UV Flame Detector

The SENSE-WARE UV (Ultraviolet) Flame Detector utilizes a microprocessor for sophisticated electronic signal analysis. The UV flame detector is suitable for indoor applications, such as fume hoods and hydrogen storages. Because of its non-corrosive housing it is suitable for indoor industrial areas were corrosion may play a role. UV (Ultraviolet) energy is emitted in practically every fire; both hydrocarbon and non- hydrocarbon fires. The ultraviolet flame detector will alarm to Arc Welding.

 

SENSE-WARE UV Flame Detector

Product specifications UV Flame detector

  • Sensitive to virtually all fires including Hydrogen Flames
  • The UV flame detector is resistant to artificial- and sunlight
  • Automatic sensor test
  • Ultraviolet flame detectors are suitable for indoor and outdoor applications
  • Operating temp.: -40 to +70°C (in Safe Area’s only)
  • GRP housing
  • Relay output for Alarm and Fault
  • Sinking 4-20 mA output (stepped)
  • CPR-EN54-10 certified
  • FM class 3260 approved
  • ATEX certified: II 3G  Ex nA IIC T4 Gc, II 3D Ex tc IIIC T 71°C Dc IP65, ambient temp.: -25 to +70°C
  • cFMus class 3611 (Nonincendive, Class I, II and III, Div 2), ambient temp.: -25 to +70°C

 

Ultraviolet flame detector Models

  • UV-185/5CZ, with CPR/EN54-10 approval and suitable for ATEX cat. 3 for zone 2/22, FM class 3260 and cFMus class 3611 Approved.

 

Literature

 

Certificates

  • CPR/EN54-10 (pdf)
  • ATEX cat. 3 for zone 2/22 (pdf)
  • FM class 3611 and 3260 (pdf)